Research progress of online monitoring techniques for dissolved gas analysis in insulating oil
作者:Hua Mao, Fangqiang Wang, Jie Wang, Zeyao Ma, Yan Wang, Rui Peng, Zhi Geng, Xinsheng Lan · 发表于:Frontiers in Chemistry · 年份:2025 · DOI:10.3389/fchem.2025.1721893 · 被引用次数:5 · 研究领域:Power Transformer Diagnostics and Insulation、High voltage insulation and dielectric phenomena、Lubricants and Their Additives
Dissolved gas analysis (DGA) in insulating oil can achieve early warning of local discharge, overheating or arc failure in transformers. It can also quantitatively evaluate the aging degree of insulating equipment, providing a basis for formulating predictive maintenance strategies, so as to improve the reliability of power grid power supply. At present, the existing common offline detection methods take a long time, and the dissolved gases in transformers are usually flammable and explosive, posing potential hazards to on-site maintenance personnel. Therefore, it is urgent to develop online detection methods for DGA. This article introduces the types and milestone research progress of DGA online detection methods in recent years (2019-2025). The instant sensing methods of dissolved gas in transformer oil are summarized and analyzed, including on-line gas chromatography analysis system, spectral analysis, and gas sensor methods. Through summarizing the advantages of different methods in terms of detection limit, response speed, operation and maintenance cost, etc., it puts forward the development trend of promoting intelligent and accurate power equipment status monitoring. This review aims to promote the further development of on-line DGA and contribute to the construction of an intelligent grid protection system by providing important technical insights.