Single Phase Grounding Fault Location Method based on the Change of the Zero Sequence Current Along with Compensation Degree
作者:Qingpu Xiao, Longyu Qin · 发表于:2021 IEEE 5th Conference on Energy Internet and Energy System Integration (EI2) · 年份:2021 · DOI:10.1109/ei252483.2021.9713374 · 被引用次数:4 · 研究领域:Power Systems Fault Detection、Islanding Detection in Power Systems、Smart Grid Security and Resilience
Single phase grounding faults occur frequently in distribution networks, which is hard to detect and locate especially those faults grounded via high impedance. This paper proposes a single phase grounding fault location method based on the change of steady state zero sequence current along with the compensation degree. Firstly, the distribution law of zero sequence current along the line for the single phase grounding fault in ungrounded system is analyzed. The correlation of the zero sequence current change with the compensation degree is also analyzed. Then the method of distinguishing grounded fault and disconnection fault is obtained. Finally, the fault location process is summarized. The simulation results show that the correctness of the location principle is not affected by the grounding impedance and the number of grounding lines.