Scholay

学术搜索 · AI 审稿 · LaTeX 协作

Thermodynamic Evaluation of LiCl-H2O and LiBr-H2O Absorption Refrigeration Systems Based on a Novel Model and Algorithm

作者:Jie Ren, Zuoqin Qian, Zhimin Yao, Nianzhong Gan, Yujia Zhang · 发表于:Energies · 年份:2019 · DOI:10.3390/en12153037 · 被引用次数:49 · 研究领域:Adsorption and Cooling Systems、Thermodynamic and Exergetic Analyses of Power and Cooling Systems、Refrigeration and Air Conditioning Technologies

An absorption refrigeration system (ARS) is an alternative to the conventional mechanical compression system for cold production. This study developed a novel calculation model using the Matlab language for the thermodynamic analysis of ARS. It was found to be reliable in LiCl-H2O and LiBr-H2O ARS simulations and the parametric study was performed in detail. Moreover, two 50 kW water-cooled single effect absorption chillers were simply designed to analyze their off-design behaviors. The results indicate that LiCl-H2O ARS had a higher coefficient of performance (COP) and exergetic efficiency, particularly in the lower generator or higher condenser temperature conditions, but it operated more restrictively due to crystallization. The off-design analyses revealed that the preponderant performance of LiCl-H2O ARS was mainly due to its better solution properties because the temperature of each component was almost the same for both chillers in the operation. The optimum inlet temperature of hot water for LiCl-H2O (83 °C) was lower than that of LiBr-H2O (98 °C). The cooling water inlet temperature should be controlled within 41 °C, otherwise the performances are discounted heavily. The COP and cooling capacity could be improved by increasing the temperature of hot water or chilled water properly, contrary to the exergetic efficiency.